OxfordAQA International GCSE Physics: Transformers and the National Grid (9203) – Revision Notes

Condensed revision notes on transformers, the grid, turns ratios and switch mode transformers for OxfordAQA International GCSE Physics, with a self-test.

Subject
Physics
Level
IGCSE
Topic
Transformers and the National Grid
Updated

Aligned to OxfordAQA IGCSE Physics (9203), For exams May/June 2018 onwards. Official specification .

Syllabus page (what it covers and how it is assessed): OxfordAQA IGCSE Physics.

Syllabus points this page covers

9203

  • 3.6.2 Electricity transmission and distribution

Found an error? Report a correction.

Need help with this topic? Request a free trial class for IGCSE Physics (9203).

These notes condense section 3.6.2 (electricity transmission and distribution) of the OxfordAQA International GCSE Physics (9203) specification, for exams May/June 2018 onwards. For full explanations read the study guide, then test yourself with the practice questions.

Other useful pages: the course hub, the printable checklist, the 10-minute diagnostics and the exam preparation page.

The system in one line

Power station, then step-up transformer, then transmission cables, then step-down transformer(s), then consumers. Transformers are at both ends of the cables (3.6.2 a). Be ready to label an unlabelled diagram of this chain.

Why high voltage (3.6.2 b)

Say it as a chain, every link:

  1. Power = potential difference × current, so for the same power a higher voltage means a lower current.
  2. A lower current means less heating in the resistance of the cables.
  3. Less energy is wasted as heat, so the system is more efficient.

Extra detail you can use: the power lost in a cable is I² × R, so halving the current cuts the loss to one quarter.

Transformer structure and operation (3.6.2 c)

Part What it is
Primary coil Input coil, connected to the supply
Secondary coil Output coil, connected to the load
Soft iron core Joins the coils magnetically and carries the changing field

Operation in steps

  1. Alternating current in the primary coil gives a changing magnetic field.
  2. The field in the iron core also passes through the secondary coil.
  3. The changing field induces a changing potential difference across the secondary coil.
  4. In a complete circuit, an alternating current flows in the secondary coil.

Laminations and eddy currents are not required. A transformer needs ac (or a changing current) because only a changing field induces a potential difference.

Step-up and step-down (3.6.2 d)

Type Vs compared with Vp Turns Where used
Step-up Vs greater than Vp ns greater than np Before the distribution lines
Step-down Vs less than Vp ns less than np At the end, for a safer voltage for local consumers

Formulas (3.6.2 e and f)

Relationship Equation Use when
Turns ratio Vp / Vs = np / ns Finding a voltage or a number of turns
100% efficient transformer Vp × Ip = Vs × Is Finding a current
Power P = V × I Finding current from power
Cable heating power lost = I² × R Comparing losses

The turns ratio is selected to produce the required output from the input.

Method in steps: turns ratio

  1. Write the equation Vp / Vs = np / ns.
  2. Put in the three values you know with units.
  3. Rearrange for the unknown.
  4. Check the direction: more turns on the secondary means a bigger secondary voltage.

Reminder. A transformer has Vp = 1500 V, np = 600 and Vs = 75 V. Find ns.

ns = np × Vs / Vp = 600 × 75 / 1500 = 30 turns

The primary-to-secondary ratio is 20 : 1, so this is a step-down transformer.

Method in steps: current across a transformer

  1. Find the power from the side you know: P = V × I.
  2. For a 100% efficient transformer the other side has the same power.
  3. Divide by the voltage on that side.

Reminder. A 100% efficient step-down transformer delivers 6.0 V at 2.0 A. The primary voltage is 12 V. Power is 6.0 × 2.0 = 12 W, so Ip = 12 / 12 = 1.0 A. Note that the primary current is smaller than the secondary current because the voltage was higher.

Switch mode transformers (3.6.2 g)

  • High frequency, often between 50 kHz and 200 kHz.
  • Much lighter and smaller than traditional transformers that work from a 50 Hz mains supply, so useful in applications such as mobile phone chargers.
  • Use very little power when switched on but with no load applied.

Must-know distinctions

Pair Difference
Primary and secondary Input coil and output coil
Step-up and step-down Output voltage greater than input, or less than input
Voltage and current across a transformer One goes up as the other goes down, with power unchanged for a 100% efficient transformer
Transmission cable and local distribution High voltage over long distances, then lowered to a safer voltage for consumers
Traditional and switch mode 50 Hz mains and heavy, or high frequency, light and small

Method in steps: comparing cable losses

  1. Convert the power and voltages to W and V.
  2. Find each current from I = P / V.
  3. Find each loss from I² × R, or compare the currents and square the ratio.
  4. Finish with a sentence saying which is more efficient and why.

Reminder. A farm sends 2.7 MW through a cable of resistance 3.0 Ω. At 90 kV the current is 2 700 000 / 90 000 = 30 A, so the loss is 30² × 3.0 = 2700 W. At 270 kV the current is 10 A, so the loss is 10² × 3.0 = 300 W. Tripling the voltage cut the current to one third and the loss to one ninth.

Command words for this unit

Command word What your answer needs
Label Name each part of the chain in the right place on the diagram
State A short fact, such as the three features of a switch mode transformer
Describe What a transformer is made of and what happens in it, in order
Explain A reason joined to a cause, such as high voltage, then low current, then less heating
Calculate Equation, substitution, answer with unit

Answer templates

Why is electricity transmitted at a high voltage? For a given power, a high voltage means a low current. A low current heats the cables less. Less energy is lost, and efficiency rises.

How does a transformer work? The primary coil carries an alternating current, so the magnetic field in the soft iron core keeps changing. The core links this field to the secondary coil, where a changing potential difference is induced. A complete circuit lets an alternating current flow there.

Why is a step-down transformer used near homes? To reduce the potential difference to a safer value for local consumers.

Quick self-test

  1. A transformer has 920 turns on the primary and 40 turns on the secondary. The primary voltage is 230 V. Find the secondary voltage.
  2. A transformer with 50 turns on the primary is connected to 12 V. The output is 480 V. How many turns are on the secondary?
  3. A 100% efficient transformer supplies 9.0 W at 150 V. What is the secondary current?
  4. A 100% efficient transformer has a primary of 150 V and 0.20 A. The secondary is 6.0 V. Find the secondary current.
  5. For the same power, the transmission voltage is raised four times. By what factor does the cable current change, and what happens to the heat loss?
  6. Name the three main parts of a basic transformer.
  7. Why does a transformer not work when its primary is connected to a battery with a steady current?
  8. Is the transformer in question 2 step-up or step-down? Give a reason.
  9. State two features of a switch mode transformer that make it useful in a phone charger.
  10. State where step-down transformers are used in the grid, and why.

Answers

  1. Vs = Vp × ns / np = 230 × 40 / 920 = 10 V.
  2. ns = np × Vs / Vp = 50 × 480 / 12 = 2000 turns.
  3. Is = P / V = 9.0 / 150 = 0.060 A.
  4. Input power = 150 × 0.20 = 30 W. Is = 30 / 6.0 = 5.0 A.
  5. The current falls to one quarter. The loss (I² R) falls to one sixteenth, because (1/4)² = 1/16.
  6. Primary coil, secondary coil and a soft iron core.
  7. Direct current from a battery gives a field that stays constant. Only a changing field induces a potential difference in the secondary coil.
  8. Step-up: the output (480 V) is greater than the input (12 V), and the secondary has more turns.
  9. Any two of: much lighter and smaller than a traditional transformer, uses very little power when switched on with no load, operates at high frequency (50 kHz to 200 kHz).
  10. At the end of the distribution, to reduce the voltage to a safer value for local consumers.

Where marks are usually lost

  • Leaving out the link between high voltage and low current in an answer on grid losses.
  • Calling the output coil “the primary”, or the reverse.
  • Writing that a step-up transformer “increases the power” or “makes more energy”.
  • Inverting the turns ratio and getting a step-up answer for a step-down transformer.
  • Forgetting to convert kV or MW before substituting.
  • Giving no unit, or the wrong unit (watts for current, for example).
  • Saying a transformer can run from a battery without mentioning the changing field.
  • Listing only “it is smaller” for switch mode transformers without relating it to the phone charger or to no-load power.
  • Not labelling transformers as step-up or step-down on a grid diagram.

Official syllabus

OxfordAQA International GCSE Physics (9203), specification for exams May/June 2018 onwards, published by OxfordAQA, section 3.6.2.

Get free revision emails (optional)

Occasional emails with practice questions, worked explanations and links to free resources for the qualification and subjects you choose. No spam, and you can unsubscribe from any email. The free tools on this site never need an email.

Subjects (optional, up to 6)

Choose a qualification to see its subjects.

Related resources

Related articles

Studying this with a teacher

Working through Physics IGCSE?

This page is free and stays free. If you would rather be taught it, Marlbridge runs Physics classes one-to-one and in small groups of up to 15, online in your own time zone. The first trial class is free. WhatsApp replies within an hour (8am–11pm Pakistan time, every day); email the same day.

OxfordAQA Physics teachers at Marlbridge